No. | Rated current | Initial state | Test current | Time limit | Expected result |
1 | In≤63 | Cold state | 1.13In | t≤1h | Not tripping |
In>63 | t≤2h | ||||
2 | In≤63 | Just followed the last test item | 1.45In | t<1h | Tripping |
In>63 | t<2h | ||||
3 | In≤32 | Cold state | 2.55In | 1s | Tripping |
In>32 | 1s | ||||
4 | Type C | Cold state | 5In | t≤0.1s | Not tripping |
10In | t<0.1s | Tripping |