Technical parameters of 10kv S9 and S9-M series off-circuit-tap-changing distribution transformers
Rated capacity kVA |
voltage combination |
no-load loss W |
load loss W |
No-load current % |
Short circuit resistance % |
weight kg |
Track gauge mm |
overall dimensions L×W×H |
High voltage kV |
tapping range |
Low voltage kV |
Connection symbol |
Tare weight |
insulating oil weight |
Total weight |
10 |
6 6.3 10 10.5 11 |
±2×2.5% or ±5% |
0.4 |
Yyn0 or Dyn11 |
70 |
300 |
2.4 |
4.0 |
75 |
50 |
175 |
400×400 |
680×450×910 |
20 |
100 |
500 |
2.3 |
115 |
65 |
235 |
400×400 |
720×580×960 |
30 |
130 |
600 |
2.1 |
150 |
70 |
300 |
400×400 |
770×600×1000 |
50 |
170 |
870 |
2.0 |
215 |
95 |
405 |
400×400 |
840×610×1030 |
63 |
200 |
1040 |
1.9 |
240 |
100 |
445 |
400×450 |
845×630×1050 |
80 |
250 |
1250 |
1.8 |
285 |
110 |
505 |
400×400 |
890×640×1070 |
100 |
290 |
1500 |
1.6 |
330 |
115 |
570 |
400×450 |
1060×620×1140 |
125 |
340 |
1800 |
1.5 |
375 |
135 |
650 |
400×550 |
1120×630×1180 |
160 |
400 |
2200 |
1.4 |
465 |
150 |
735 |
550×550 |
1200×645×1170 |
200 |
480 |
2600 |
1.3 |
525 |
160 |
895 |
550×550 |
1250×660×1210 |
250 |
560 |
3050 |
1.2 |
655 |
200 |
1075 |
550×650 |
1320×740×1270 |
315 |
670 |
3650 |
1.1 |
730 |
235 |
1240 |
550×650 |
1345×760×1305 |
400 |
800 |
4300 |
1.0 |
860 |
265 |
1375 |
550×650 |
1395×780×1360 |
500 |
960 |
5150 |
1.0 |
1060 |
340 |
1705 |
660×750 |
1520×840×1390 |
630 |
1200 |
6200 |
0.9 |
4.5 |
1225 |
350 |
2015 |
660×750 |
1535×850×1455 |
800 |
1400 |
7500 |
0.8 |
1430 |
440 |
2405 |
820×850 |
1650×950×1540 |
1000 |
1700 |
10300 |
0.7 |
1555 |
470 |
2500 |
820×850 |
1820×1100×1580 |
1250 |
1950 |
12000 |
0.6 |
1820 |
620 |
3170 |
820×850 |
1840×1120×1605 |
1600 |
2400 |
14500 |
0.6 |
2220 |
640 |
4600 |
820×900 |
1930×1160×1780 |
2000 |
2900 |
17500 |
0.6 |
3095 |
975 |
5600 |
820×900 |
1980×1180×1950 |
Rated capacity kVA |
voltage combination |
no-load loss W |
load loss W |
No-load current % |
Short circuit resistance % |
weight kg |
Track gauge mm |
overall dimensions L×W×H |
High voltage kV |
tapping range |
Low voltage kV |
Connection symbol |
Tare weight |
insulating oil weight |
Total weight |
630 |
6 6.3 10 10.5 11 |
±2×2.5% or ±5% |
3 3.15 6.3 |
Yd11 |
1200 |
6200 |
1.4 |
4.5 |
1430 |
410 |
3185 |
660×750 |
1690×965×1440 |
800 |
1400 |
7500 |
1.3 |
5.5 |
1640 |
665 |
3090 |
820×820 |
1885×1160×2125 |
1000 |
1700 |
10300 |
1.2 |
1900 |
700 |
3300 |
820×820 |
1925×1240×2710 |
1250 |
1950 |
12000 |
1.2 |
2180 |
870 |
4150 |
820×820 |
2010×1540×2180 |
1600 |
2400 |
14500 |
1.1 |
2720 |
900 |
4860 |
820×820 |
2100×1760×2305 |
2000 |
2900 |
17500 |
0.9 |
3000 |
940 |
5230 |
1070×1070 |
2120×1860×2315 |
2500 |
3430 |
20200 |
0.9 |
3435 |
1120 |
5755 |
1070×1070 |
2140×2056×2365 |
3150 |
4140 |
23700 |
0.8 |
4000 |
1550 |
7200 |
1070×1070 |
2470×2770×2555 |
4000 |
3.15 6.3 |
4980 |
28100 |
0.7 |
4790 |
1620 |
8500 |
1070×1070 |
2720×2480×2860 |
5000 |
6020 |
32300 |
0.7 |
5740 |
1730 |
9515 |
1070×1070 |
2810×2560×2920 |
6300 |
7050 |
36000 |
0.6 |
7410 |
2050 |
11610 |
1070×1070 |
2850×2930×3010 |
Technical parameters of 10kv S11 series off-circuit-tap-changing distribution transformers
Rated capacity kVA |
voltage combination |
no-load loss W |
load loss W |
No-load current % |
Short circuit resistance % |
weight kg |
Track gauge mm |
overall dimensions L×W×H |
High voltage kV |
tapping range |
Low voltage kV |
Connection symbol |
Tare weight |
insulating oil weight |
Total weight |
30 |
6 6.3 10 10.5 11 |
±2×2.5% or ±5% |
0.4 |
Yyn0 or Dyn11 |
100 |
600 |
2.1 |
|
150 |
75 |
320 |
400×400 |
730×480×950 |
50 |
130 |
870 |
2.0 |
210 |
89 |
370 |
400×400 |
758×510×920 |
63 |
150 |
1040 |
1.9 |
255 |
95 |
420 |
400×450 |
788×530×950 |
80 |
180 |
1250 |
1.8 |
280 |
120 |
490 |
400×450 |
808×580×970 |
100 |
200 |
1500 |
1.6 |
360 |
125 |
600 |
400×550 |
830×760×1160 |
125 |
240 |
1800 |
1.5 |
410 |
135 |
690 |
400×550 |
990×620×1040 |
160 |
290 |
2200 |
1.4 |
480 |
155 |
815 |
550×550 |
1070×680×1100 |
200 |
330 |
2600 |
1.3 |
563 |
168 |
920 |
550×550 |
1170×770×1300 |
250 |
400 |
3050 |
1.2 |
665 |
200 |
1020 |
550×550 |
1230×820×1190 |
315 |
480 |
3650 |
1.1 |
751 |
230 |
1160 |
550×550 |
1295×865×1240 |
400 |
570 |
4300 |
1.0 |
880 |
235 |
1385 |
550×550 |
1385×925×1250 |
500 |
680 |
5150 |
1.0 |
1100 |
340 |
1670 |
660×750 |
1560×1060×1360 |
630 |
810 |
6200 |
0.9 |
4.5 |
1300 |
380 |
1920 |
660×750 |
1615×1105×1350 |
800 |
900 |
7500 |
0.8 |
1585 |
465 |
2330 |
820×850 |
1725×1190×1390 |
1000 |
1150 |
10300 |
0.7 |
1720 |
510 |
2680 |
820×850 |
1820×1290×1440 |
1250 |
1360 |
12000 |
0.6 |
2075 |
625 |
2995 |
820×850 |
1860×1290×1540 |
1600 |
1640 |
14500 |
0.6 |
2215 |
640 |
3615 |
820×900 |
1340×1700×1560 |
Insulation level
Model |
Voltage grade |
Rated short-duration power-frequency withstand voltage (effective value) |
Rated lightning impulse withstand voltage (peak value) |
S9 S11
S9-M SZ9 S11
SZ9-M |
6 |
25 |
60 |
10 |
35 |
75 |
35 |
85 |
200 |
Technical parameters of 10kv S11-M-D series off-circuit-tap-changing underground distribution transformers
Rated capacity kVA |
voltage combination |
no-load loss W |
load loss W |
No-load current % |
Short circuit resistance % |
weight kg |
Track gauge mm |
overall dimensions L×W×H |
High voltage kV |
tapping range |
Low voltage kV |
Connection symbol |
Tare weight |
insulating oil weight |
Total weight |
50 |
6 6.3 10 10.5 11 |
±2×2.5% or ±5% |
0.4 |
Yyn0 or Dyn11 |
130 |
870 |
2.0 |
4.0 |
245 |
165 |
555 |
550×550 |
891×748×1144 |
63 |
150 |
1040 |
1.9 |
295 |
180 |
640 |
550×550 |
906×630×1204 |
80 |
180 |
1250 |
1.8 |
340 |
195 |
710 |
550×550 |
926×780×1239 |
100 |
200 |
1500 |
1.6 |
405 |
215 |
830 |
550×550 |
951×945×1284 |
125 |
240 |
1800 |
1.5 |
470 |
230 |
915 |
550×550 |
971×875×1334 |
160 |
280 |
2200 |
1.4 |
545 |
260 |
1065 |
550×550 |
996×1045×1389 |
200 |
340 |
2600 |
1.3 |
635 |
285 |
1210 |
550×550 |
1041×1060×1419 |
250 |
400 |
3050 |
1.2 |
730 |
325 |
1395 |
550×550 |
1071×1230×1504 |
315 |
480 |
3650 |
1.1 |
850 |
365 |
1610 |
660×660 |
1106×1405×1584 |
400 |
570 |
4300 |
1.0 |
1030 |
395 |
1880 |
660×660 |
1146×1180×1649 |
500 |
680 |
5150 |
1.0 |
1180 |
430 |
2110 |
660×660 |
1181×1270×1689 |
630 |
810 |
6200 |
0.9 |
4.5 |
1490 |
535 |
2725 |
820×820 |
1300×1475×1748 |
800 |
980 |
7500 |
0.8 |
1710 |
610 |
3105 |
820×820 |
1330×1665×1793 |
1000 |
1150 |
10300 |
0.7 |
1905 |
695 |
3590 |
820×820 |
1360×1920×1868 |
Overall dimensions of transformers
Frequently Asked Question (FAQ)
Q:
About the company
A: Westhomes® is a professional manufacturer for low voltage and high voltage electrical products with a thirty-year history.
Main supplier of state-owned companies like China Stae Grid, China Southern Power Grid through bidding with bunches of test certificates, sales records and operation performance to support.
Enough investment for research and development for the products innovation.
Q:
About Warranty
A: 18 months from the date of receivement
Q:
About shipment method
A: Depends on the required quantity and delivery urgency, both international express like UPS / DHL / EMS / HK EMS / FedEx / TNT (door to door service) and normal sea shipping & air freight also avaliable.
Q:
About MOQ
A: Upto the client
Q:
About payment method
A: We accept T/T, Paypal, Western union, L/C. Normally 30% payment in advance, 70% before delivery.
Q:
About ordering process
A: First to send an inquiry via made-in-china platform or directly to the contact e-mail address. All the following thing is the communication between us.
Contact
Ms Stephanie Huang
Senior Sales Manager
Add: Liushi Town, Yueqing City, Zhejiang Provine, China 325604
http://westhomes.en.made-in-china.com/
Mob: 0086-1386832836